Fixed point gas detector smart XgardIQ

Buyer Rates Mã sản phẩm: 17365

Model: XgardIQ
Manufacturer: Crowcon
Status: Stocking
Guarantee: 12 months
Price: Contact

May-do-khi-diem-co-dinh-thong-minh-xgardiq-Crowcon May-do-khi-diem-co-dinh-thong-minh-xgardiq-Crowcon

The XgardIQ Smart Fixed Point Gas Detector is our latest gas detector, increasing safety by reducing the time operators have to spend in hazardous areas.

This versatile gas generator and generator has a range of features that protect engineers and facility managers supporting oil, gas, chemical & petrochemical plants.

Available with a variety of flammable, toxic or oxygen sensors.

(SIL-2) Certified class 2 safety gas detector.

Description

I. Specification of XgardIQ intelligent fixed point gas detector

Fixed point gas detector smart XgardIQ

Generality:

  • The XgardIQ Versatile Intelligent Fixed Gas Detector is a smart and versatile gas generator and transmitter compatible with Crowcon’s full range of sensor technologies. Available with a variety of flammable, toxic or oxygen sensors.
  • Providing the same 4-20mA and RS-485 Modbus signals as standard, the XgardIQ Smart Fixed Point Gas Detector is optionally available with Alarm and Fault relays and HART communication. 316 stainless steel is available with three M20 or 1/2″ NPT cable entries.
  • (SIL-2) certified class 2 safety gas detector.

Easy and safe to use:

  • OLED Display – Bright, clear display indicates gas level and detection status even in dark locations.
  • Non-Intrusive Calibration – No and calibration is performed through the display and keypad, without the need for a hot work permit or any special tools (e.g. no magnetic wand)
  • + ve Safety Indicator – Confirm the detector is working safely at a glance
  • Event logging function – The XgardIQ smart fixed point gas detector stores all alarm, fault and maintenance events to provide a history of detector usage
  • Remote sensing – Improved detection probability.

Fixed point gas detector smart XgardIQ

Simple installation and maintenance:

  • All-in-one Transmitter – Universal transmitter for all of Crowcon’s sensor technology
  • Hot-swap sensor modules – Sensors can easily be replaced with one hand without tools or hot work permits
  • Auto Sense Function – Automatically detects whether the control system is a 4-20mA current source or source and sets itself appropriately, eliminating the risk of being set incorrectly
  • Auto-configuration function – Detects when the sensor module is plugged in and uploads the appropriate gas type, range, units and alarm levels.

High reliability:

  • Smart Bump and Rapid Bump Test Functions – The XgardIQ Smart Fixed Point Gas Detector enables quick and easy verification of sensor capability and response using the test gas. The process is automated and provides reminders when checking the bump.
  • Calibration Alerts – Remind users when calibration is due to ensure that sensors remain functional and accurate at all times
  • Sensor Range Selection – User can set full sensor range through display menu according to specific location or location requirements.

Fixed point gas detector smart XgardIQ

***You may be interested in other gas analyzers from GMGA: https://gmga.vn/en/danh-muc/analytical-equipment/gas-analysis-equipment/

II. Specifications of the XgardIQ universal intelligent fixed gas detector

Size H278 x W140 x D89mm (10.9 x 5.5 x 3.5 in)
Weight 4.1Kg (9lbs)
Enclosure material 316 stainless steel
Ingress protection IP66
Connection Three M20 or ½”NPT cable gland entries.Certified, removable plugs are fitted to left-hand and lower righthand entries
Power 14-30 VDC. <4W
Display Main display – OLED 128 x 64 pixels, yellow text on black background
Indicators – Amber, Red and Green LED’s for detector status; Blue +ve Safety LED
Electrical output 4-20mA current sink or source (Auto-Sense or manual selection); warning and fault signals are configurable. NAMUR NE 43 compliant
RS-485 Modbus RTU
HART 7 over 4-20mA signal and via local I.S. test points (optional)
Relays (optional)
Alarm 1, Alarm 2, Fault
SPCO contacts rated 5A, 230Vac
Relay configuration options
Energised or de-energised
Latching or non-latching
Rising or falling
Configurable On and Off delays on alarm relays.
Event logging Records alarm, fault and maintenance events. Events can be viewed on-screen and downloaded to a PC.
Operating temperature Transmitter only: -40°C to +75°C (-40°F to +167°F)†
Sensor type:
Oxygen: (-20°C to +50°C ambient)
Toxic: (-40°C to +50°C ambient)
Pellister: (-40°C to +75°C ambient)
Infra-red (IR): (-20°C to +55°C ambient)
High temperature toxic:  (-40⁰C to +70⁰C)
Humidity 0 to 95% RH non-condensing†
Repeatability +/- 2% FSD
Zero drift +/- 2% FSD per year maximum
Response time Sensor dependant: contact Crowcon for specific sensor data.
Approvals ATEX and IECEx:
Ex II 2 G    Ex db ia IIC T4 Gb (see above for temperature ranges)
Performance Designed for compliance with:
EN50104 (oxygen sensors)
EN45544 (toxic gas sensors)*
EN50271 (software)
H2S performance standard
Functional safety IEC61508, EN50402 SIL 2
EMC Compliance EN50270:2015
FCC CFR47 Part 15B
ICES-003
† Note: sensor operating temperature and humidity limits vary widely.
* Features outstanding at the time of issue, contact Crowcon for details.

Gas And Range

Gas

Units Max Standard Alarm 1 Alarm 2 Temp
Range Range level level

range °C 

Oxygen (O2)

%Vol 30 25 19 (falling) 17 (falling) -20 to +50
Ammonia PPM 100/1000 50 25 35

-20 to +40

 Carbon Monoxide (CO)

PPM 1000 250 30 200  -30 to +50
Hydrogen Fluoride (HF) PPM 10 10 1.8 3

+5 to +40

Hydrogen Sulphide (H2S)

PPM 100/200 25 5 10 -30 to +50
High Temperature Hydrogen Sulphide (H2S) PPM 100/200 25 5 10

-40 to +70

Ozone (O3)

PPM 1 1 0.1 0.2 -20 to +40
Sulphur Dioxide (SO2) PPM 100 10 1 1

-30 to +50

Hydrogen (H2)

%LEL 100 100 20 40 -40 to +75
Methane (CH4) %LEL 100 100 20 40

-40 to +75

Pentane (C5H12)

%LEL 100 100 20 40 -40 to +75
Propane (C3H8) %LEL 100 100 20 40

-40 to +75

Ethanol (IR sensor)

%LEL 100 100 20 40 -20 to +55
LPG (IR sensor) %LEL 100 100 20 40

-20 to +55

Methane (IR sensor)

%LEL 100 100 20 40 -20 to +55
Propane (IR sensor) %LEL 100 100 20 40

+10 to + 55

 

III. Video

 

***Product main path: XgardIQ Fixed Detector

Reviews

There are no reviews yet.

Be the first to review “Fixed point gas detector smart XgardIQ”

Your email address will not be published.